Summary
- Cooling readiness is becoming part of sovereign-compute readiness in India. India’s AI procurement increasingly evaluates outcomes such as PUE, availability, domestic hosting, and sustained operating performance, all of which cooling design can influence.
- The GPU platform can determine the thermal architecture. As rack-scale systems become denser, operators may need direct-to-chip or hybrid cooling and must plan CDUs, coolant flow, controls, leak detection, and facility heat rejection around the selected compute platform.
- Liquid cooling performance depends on the full thermal path. Engineers must design cold plates, CDUs, HDUs, rear-door heat exchangers, chillers, and heat rejection together to support rack density, efficiency, water use, and availability under Indian operating conditions.
- Bid readiness requires more than installed cooling capacity. Specifications, redundancy, coolant management, telemetry, commissioning, and clear ownership across OEMs, contractors, controls teams, and operators all affect whether high-density GPU capacity can perform as required.
Author: Sumati Sahgal, VP, Data Centre & Secure Power, Greater India
India’s sovereign-compute procurement does not explicitly mandate liquid cooling. However, cooling is increasingly tied to bid readiness for data centre operators and the partners designing their infrastructure.
IndiaAI increasingly evaluates outcomes influenced by cooling design, including facility efficiency, availability, domestic deployment, and the ability to bring new GPU capacity online on a scale. At the same time, newer rack-scale GPU systems are pushing thermal loads beyond what many conventional air-cooled environments can handle.
For a GPU data centre in India, cooling needs to be considered alongside the compute platform from the start. The facility must support its thermal load, efficiency requirements, and availability commitments under Indian operating conditions.
IndiaAI increasingly measures outcomes influenced by cooling
IndiaAI’s procurement requirements show how cooling has become part of infrastructure competitiveness. In 2024, the programme briefly introduced an operating data-centre PUE of 1.35 or below as an eligibility requirement. The industry later removed that threshold following feedback. Graded PUE scoring remained, with progressively higher technical scores for lower PUE and the highest score available below 1.2.
Efficiency also carries into operations. The continuous empanelment framework requires quarterly compliance reporting, and PUE improvements can reduce certain penalties. IndiaAI applies service credits when availability falls below 99.95%.
Those requirements put sustained cooling performance under greater scrutiny. Pumps, controls, coolant distribution, leak detection, and heat rejection all affect a high-density facility’s operating performance. Domestic hosting adds another constraint. IndiaAI requires AI services to be delivered from data centres in India, so infrastructure planning must account for local climate, utility, and water conditions.
Procurement gives providers flexibility in how they achieve those outcomes. Air cooling can remain suitable for some systems, while direct-to-chip and hybrid architectures become necessary as rack density increases.

The GPU data centre platform can set the cooling requirements
Hardware selection can narrow those cooling choices considerably. In the fourth IndiaAI procurement round, reporting reviewed for the research identified an offer of 17,000 NVIDIA B300 GPUs.
The B300 offer provides a current link to IndiaAI procurement, while NVIDIA’s Vera Rubin platform shows how quickly thermal requirements are increasing. Vera Rubin NVL72 combines 72 Rubin GPUs and 36 Vera CPUs in a rack-scale system. Vera Rubin significantly raises the cooling capacity GPU data-centre operators in India must plan for as newer GPU platforms enter deployment.
At these densities, GPU procurement creates requirements beyond the servers themselves. Cold plates, manifolds, coolant flow, CDU capacity, controls, leak detection, and facility heat rejection all must be planned around the selected platform. The GPU choice can lock the project into a specific thermal architecture early in the deployment cycle. Data centre operators must confirm that the proposed hall can provide the required cooling capacity, redundancy, and facility connections at the intended rack locations.
This also limits the value of broad “AI-ready” claims. Customers need specific information on supported rack densities, available liquid loops, residual air-cooling requirements, heat-rejection capacity, and commissioning procedures.
IndiaAI’s empaneled infrastructure spans several GPU generations and vendors, so cooling requirements will vary across deployments. Designing around the server architecture provides a more reliable basis than applying one cooling approach across every GPU environment.
Liquid cooling for GPU data centres in India extends from the chip to heat rejection
Direct-to-chip cooling begins at the processor, but its performance depends on the full thermal path. Cold plates capture heat from high-power components. A Coolant Distribution Unit (CDU) provides the interface between the technology cooling system serving the IT equipment and the facility water system. It manages heat exchange, temperature, pressure, flow, filtration, and coolant condition.
In facilities with suitable water infrastructure, liquid-to-liquid CDUs can connect the secondary loop to the building mechanical plant. Brownfield sites may require other approaches. Heat Dissipation Units (HDUs) or liquid-to-air configurations can introduce liquid-cooled IT where a usable facility-water connection is unavailable. They transfer heat back into the room or air-side cooling system, so the facility still needs sufficient capacity to remove that heat.
Rear-door heat exchangers can support appropriate retrofit and hybrid environments, particularly where residual air heat remains. They should be evaluated against the thermal requirements of the specific rack architecture. High-density rack-scale systems may still require direct-to-chip cooling even when rear-door heat exchangers are used elsewhere in the hall.
Facility-side chillers and heat rejection complete the thermal chain. Their design is especially important in India because high ambient temperatures reduce cooling efficiency and limit chiller-less operation.
The design also requires careful water treatment. A closed liquid loop serving the IT equipment can recirculate coolants without significant ongoing consumption, while the upstream heat-rejection system may use dry, adiabatic, evaporative, or hybrid methods. Each has a different energy and water profile.
Rack cooling and facility cooling therefore need to be engineered together. Direct-to-chip accessories, CDUs, HDUs, rear-door heat exchangers, chillers, and heat rejection all influence the final combination of rack density, PUE, water use, and availability.
Bidders need specifications that cover operating performance
India AI’s PUE, availability, and reporting requirements increase the importance of resilience and measurement. Design specifications should address CDU pump and control redundancy, isolation, leak detection, alarm sequences, and recovery procedures. An efficient thermal design can still create availability risk if a critical cooling component becomes a single point of failure.
Coolant management also needs defined ownership. Specifications should cover coolant type and concentration, filtration, chemistry, material compatibility, and responsibility for maintaining fluid quality through operations.
Telemetry supports the quarterly reporting requirement. Operators need consistent measurement boundaries and visibility into IT load, cooling energy, CDU thermal capacity, temperatures, and flow. This data helps verify operating performance, so operators don’t have to rely only on design assumptions.
Commissioning should validate the complete thermal system. Factory acceptance testing, flushing and cleanliness checks, pressure and leak testing, integrated controls testing, and staged-load testing can identify problems before production workloads are introduced.
Clear ownership across the ecosystem is equally important. Server OEMs, rack integrators, cooling suppliers, MEP contractors, controls teams, commissioning agents, and facility operators all influence system performance. Compute requirements must be translated into defined thermal operating conditions. Mechanical contractors need to ensure cleanliness, hydraulic balance, and installation quality. Commissioning teams need to verify performance from the cold plate through facility heat rejection.
For operators evaluating a GPU data centre in India, design and procurement requirements often boil down to a few practical questions about cooling architecture, efficiency, and deployment readiness.
Frequently asked questions about GPU data centres in India
What cooling does a GPU data centre in India need? The answer depends on rack density and the selected compute platform. Air cooling can still suit some deployments, but higher-density GPU racks may require direct-to-chip liquid cooling or a hybrid architecture that combines liquid cooling with residual air cooling.
Why is liquid cooling important for GPU data centres in India? High-density GPU systems concentrate more heat within the rack. Liquid cooling can capture heat closer to the processors and reduce reliance on high-volume air movement, but the system still needs appropriately sized CDUs, controls, redundancy, and facility heat rejection.
How can liquid cooling affect PUE in an Indian GPU data centre? Liquid cooling can reduce energy used for server fans, air movement, and mechanical cooling, thereby lowering PUE. Actual improvement depends on rack density, liquid heat capture, local climate, operating temperatures, and facility-side cooling design.
What should operators check before deploying high-density GPU racks in India? Operators should confirm rack-level cooling requirements, CDU capacity and redundancy, coolant quality and leak detection, residual air-cooling needs, facility-water connections, heat-rejection capacity, telemetry, commissioning procedures, and the local climate and utility conditions that will shape sustained operation.
Cooling readiness is becoming part of sovereign-compute readiness
India’s sovereign GPU procurement is placing greater emphasis on PUE, availability, domestic capacity, and sustained operating performance. Dense GPU architectures are increasing thermal requirements in that procurement environment. For a GPU data centre in India, evaluate cooling alongside the compute platform. Chip-level heat capture, coolant distribution, facility-water interfaces, heat rejection, controls, redundancy, and commissioning all influence whether high-density capacity can operate as specified. Our comprehensive, end-to-end liquid cooling portfolio, now including Motivair by Schneider Electric, spans direct-to-chip accessories, CDUs, HDUs, rear-door heat exchangers, chillers, and heat rejection, along with the wider power, controls, and services required to integrate those technologies into the data centre. Schneider Electric’s Liquid Cooling Hub provides more detail on comprehensive thermal architectures. For a closer look at how to select and design the right system for your facility, download the Liquid Cooling System Architecture Guide.