Measuring the impact of prefabricated IT pods: What we learned working with Compass Datacenters

As demand for AI-ready infrastructure continues to accelerate, data center teams are under growing pressure to deliver capacity faster, with less risk and greater predictability. Together with Compass Datacenters, we set out to answer a question many in the industry have been asking: How much deployment time can actually be saved when critical white-space infrastructure is integrated into a prefabricated IT pod before arriving onsite? While the benefits are often discussed, they are not often quantified. 

To find out, we analyzed the installation of a prefabricated liquid-cooled IT pod and compared it with a functionally equivalent traditional approach in which containment, TCS piping, busway, and cable-support systems are installed onsite. The results became the foundation of our latest white paper, Prefabricated White Space Module Time Study: Lessons from a High-Density Liquid-Cooled Deployment. 

The study focused on the onsite activities required to prepare the pod for IT equipment installation. The prefabricated schedule used durations observed during a Compass Datacenters deployment. The traditional comparison combined observed containment-installation durations with schedules developed by mechanical, electrical, and plumbing (MEP) specialists for the additional TCS piping, busway, and cable-support infrastructure needed for a functionally equivalent installation. Activities after installation verification and all offsite manufacturing activities were outside the scope of the comparison. 

Why are high-density white-space installations becoming more complex?

As rack power densities increase, so does the infrastructure required to support it. Modern deployments are more often including higher-capacity power distribution, denser cable-support systems, more substantial structural supports, and the overhead piping required for liquid-cooling systems. All of these systems must coexist within the same overhead and rack-adjacent space, making coordination and installation more complex. 

Traditionally, these systems arrive as separate deliveries and are installed onsite through multiple activities. TCS piping, busway, and cable pathways may also require separate support arrangements, adding layout, alignment, elevated work, and inspection. As densities increase and available space becomes more constrained, coordinating these systems can make deployment labor-intensive, highly sequenced, and difficult to accelerate. 

Why are Prefabricated designs better approach?

Compass Datacenters has been deploying a different approach with prefabricated IT pods, or what they call white space modules. Instead of installing major infrastructure systems separately onsite, key elements are integrated onto the pod frame in a manufacturing environment before delivery. 

For the deployment studied, Schneider Electric and Compass Datacenters co-engineered a prefabricated IT pod for a high-density, liquid-cooled data hall. TCS piping, busway, cable-support infrastructure, containment, and their associated supports were incorporated into the pod design. This allows selected infrastructure to be installed, aligned, inspected, and, where applicable, tested during manufacturing while site preparation proceeds in parallel. The figure below highlights the infrastructure systems integrated onto the prefabricated IT pod. 

Figure showing infrastructure systems integrated onto a prefabricated IT pod, including integrated busway, integrated cable shelves, integrated TCS piping, and frame-mounted containment.

For the configuration analyzed, the duration decreased from 75.5 hours for the traditional approach to 15 hours for the prefabricated IT pod, representing an 80% reduction. The following chart compares the onsite installation phases for the two approaches. 

Chart comparing the onsite installation phases for traditional IT pods and prefab IT pods. Prefab IT pods have an 80% shorter installation timeline as there is no separate TCS, busway, and cable shelving installation.

The reduction did not come from crews performing the same field activities faster. In the traditional comparison, separate TCS, busway, and cable-shelving installation accounted for approximately 37, 13, and 5 hours, respectively. With the prefabricated IT pod, the truss-mounted TCS piping sections were installed before delivery and joined onsite, while the busway cages and cable shelving were mounted to the pod frame during assembly, substantially reducing separate onsite installation activities. 

Not every individual phase was shorter. The prefabricated deployment required more effort to receive and stage larger, preassembled components. In contrast, the traditional deployment involved smaller components that could be unloaded more quickly but required additional unpacking, organization, verification, and installation later in the sequence. The modest increase in front-end handling was offset by the later installation work avoided. 

What do prefabricated IT pods improve beyond deployment speed?

Our work with Compass also highlighted the broader benefits of a repeatable, factory-integrated approach. Because the prefabricated IT pod design and installation sequence are standardized, teams can refine the same core process across deployments. At Compass Datacenters, the installation analyzed required approximately 15 hours of onsite work, compared with 18 hours for a deployment completed 15 pods earlier. Reusing common designs, assembly processes, and installation sequences can improve predictability while allowing lessons learned to be incorporated into later pods. 

The approach also shifts portions of inspection and quality verification into a controlled manufacturing environment. For example, factory-installed TCS piping sections can be cleaned, passivated, and leak-tested before shipment. The complete TCS loop still requires final flushing, pressure testing, and commissioning onsite, but completing selected activities earlier reduces the amount of integration work required within the data hall. 

A standardized IT pod platform does not mean the design must remain static. During the Compass Datacenters deployment, pod configurations evolved as project requirements changed, including changes in cooling and density. Because the prefabricated IT pod had defined structural interfaces and an established installation sequence, refinements could be incorporated into later modules without entirely recoordinating the overhead supports, routing, and trade sequencing across the white space.

What did we learn by deploying prefabricated IT pods with Compass?

Compass Datacenters brought practical experience deploying repeatable white space modules at its campuses, while Schneider Electric contributed expertise in prefabricated infrastructure design and quantitative analysis. Together, these perspectives provided the deployment information and technical context needed to compare functionally equivalent prefabricated and traditional approaches. 

The resulting study moves the discussion beyond general expectations by showing where onsite installation time is reduced and why. The findings can help operators, developers, and design teams evaluate whether shifting selected work to a manufacturing environment fits their project requirements. 

Read the full white paper to explore the methodology, assumptions, detailed installation activities, and additional findings from the Schneider Electric and Compass Datacenters collaboration.  And if you’re interested in how this approach translates into solutions, explore our prefabricated data center solutions.